FAE 4 CAN

FAE 4 CAN
FAE 4 CAN
FAE 4 CAN
FAE 4 CAN
FAE 4 CAN
FAE 4 CAN

FAE 4 CAN


P/N: 1105741306

  • Color: gray
  • EAN-No: 4250184122531

CAN module with 4 temperature and 4 voltage inputs. It is suitable for recording temperatures with Ni1000 or PT1000 sensors and voltages of, for example, electrical vent and mixing valves, valve positions, etc. The fieldbus module is an input module for universal use. It is controlled by means of the CAN bus. The module is addressed by means of an adjustable address, and the input states are transmitted in data bytes. If there is one (or more) analog output module(s) with the same address in the system, the voltage measured there is issued at the respective output.Each input can be adjusted either from 0 to 10 V DC, to Ni1000 (-50 °C to +150 °C), PT1000 (-50 °C to +150 °C) or PT1000 (0 °C to +400 °C) by means of a DIP switch.

Protocol CAN
Addressing range 00 to 99
Bus interface ©CiA standard 2.0B passive (two-wire bus)
Transmission rate 20 to 500 kBit/s
Operating voltage 24 V AC/DC ± 10% (SELV)
Current consumption 67 mA (AC) / 24 mA (DC)
Relative duty cycle 100 %
Recovery time 550 ms
Inputs 4 x analog
Input / voltage 0 V to 10 V DC
Input / resolution 10 mV / (0 % to 100%)
Input / error approx. +/- 20 mV
Input / temperature range Ni1000, -50 to +150 °C
Input / temperature range PT1000, -50 to +150 °C
Input / temperature range PT1000, 0 to +400 °C
Display Green and red LED
Dimensions (W x H x D) 35 x 70 x 65 mm
Weight 84 g
Operating temperature range -5 °C to +55 °C
Storage temperature range -20 °C to +70 °C
Ingress protection for housing / terminal block IP40 / IP20